ZOS Fireproof mortar PROMASTOP TYP-S
Information:
Application:
PROMASTOP Typ S protective mortar allows making cable passages in the fire resistance Class from EI 30 to EI 120. According to the specification from the manufacturer univarsal passages are allowable with the mix of electric conduits, plastic tubes (max.200 mm), steel and cast iron tubes (max.168.3 mm).
Product description.
The mix of concrete, mortar and light additives.
Technical Approval: AT-15-5730/2007
Certificate of Conformityi: ITB 0949/W
Declaration of Conformity: DZ-22
Instructions for use.ogólne:
- Arrange a cable route through passages sealed with the ZOS type of mortar.
- The maximum allowed cable load in a passage shall not exceed 60%.
- The wall and ceiling thickness to construct a passage shall be not less than:
120mm – for concrete walls
250mm – for solid brick walls and cell concrete walls
180mm – for the ceiling
- The first of the cable route supports shall be installed at a distance not less than 100 mm from the partition.
- The maximum passage dimensions in the ceiling shall not exceed 1000 mm in width with unlimited pasage length.
- The maximum passage dimensions in the wall according to the drawing below.